Henrico County Unincorporated, Virginia · General provision
Sec. 24-4438
Extracted standards
2 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Other
- Equipment must be enclosed or screened
All equipment necessary for operating the data center must be contained within an enclosed building or screened by opaque walls to minimize transmission of sound. This includes equipment for cooling and ventilating, as well as emergency power generators and other emergency power supply equipment.
- Must be on same or adjacent premises
The accessory data center and the office or industrial use to which it is accessory must be located on the same or adjacent premises.
From the ordinance
A data center is allowed as an accessory use to an office or industrial use, subject to the following standards in addition to the standards of Sec. 24-4328.B: